Advanced Wire Tracer Kit

AT-6010

Precisely locate wire locations with the large LCD receiving screen featuring a two-digit display, bar graph and audio.

 

SKU: AT6010 Category: Tag:

Description

Easily and accurately locate wires, breakers, and fuses with the AT-6010 Advanced Wire Tracer. When the Transmitter is connected to the circuit (Energized or De-energized, up to 600 V AC/DC in Category I through Category III electrical environments), the Receiver easily detects the transmitted signal in the wires or cables behind walls, ceilings and floors. Work safely on energized circuits without the need to take equipment offline. The Transmitter also features high signal mode for general tracing and a loop mode designed specifically for locating shorts, as well as two optimal tracing frequencies that are automatically activated based on the detected voltage. The AT-6010 can be combined with the CT-400 Signal Clamp (optional accessory) for applications where access to circuit contacts is limited or where users are not able to connect the Transmitter to the circuit through test leads.

Features

  • Traces wires in walls, ceilings, floors and corners
  • Locates breakers and fuses
  • Pinpoints shorts and opens
  • High resolution 2.5″” TFT LCD black & white display
  • Simple one button Transmitter operation
  • Two Transmitter signal modes
    1. “High Signal” mode for normal circuits
    2. “Loop” mode for closed loop de-energized circuits
  • Two automatically selected frequency modes for reliable tracing on energized and de-energized circuits
  • Comes with custom Amprobe soft carrying case, test leads and accessories
  • Rated CAT III 600 V for work directly on an energized circuit without the need to take equipment offline
  • Compatible with optional Signal Clamp (CT-400) clamp-on attachment

Specifications

FeaturesAT-6010-R ReceiverAT-6010-T Transmitter
Measurement categoryCAT III 600 V
Operating voltage/current0 to 600 V
Operating frequencyEnergized: 6.25 kHz
Hazardous voltage detectionN/A> 30 V AC/DC
Signal indicationsNumeric bar graph display and audible beepLEDs
Response timeTip Sensor (Energized/De-energized): 500 ms
Battery voltage monitoring: 5 sec
Line voltage monitoring: 1 sec
Battery voltage monitoring: 5 sec
Current output of signal (typical)N/AEnergized circuit:
HI mode: 60 mA RMS
De-energized circuit:
HI mode: 130 mA RMS
Loop mode: 160 mA RMS
Signal voltage output (nominal)N/ADe-energized circuit:
HIGH: 33 V RMS, 140 Vp-p
With CT-400:
Loop model:
31 V RMS, 120 Vp-p
Range detection (open air)Tip Sensor (Energized):
Max distance via air: up to 20 ft (6.1 m)
Pinpointing: approx. 1.97 in (5 cm)
Tip Sensor (De-energized):
Max distance via air: up to 14.7 ft (4.5 m)
Pinpointing: approx. 1.97 in (5 cm)
N/A
Display sizeLCD 2.5 in (6.35 cm)N/A
Display dimensions (W x H)1.45 x 1.93 in
(36.72 x 48.96 mm)
N/A
Display typeSegment LCDLEDs
Display colorBlack and whiteOperating mode LEDs: red
Battery status LED: red
Booting time< 3 sec< 2 sec
BacklightYesN/A
Operating temperature-4 °F to 122 °F (-20 °C to 50 °C)
Operating humidity45%: -4 °F to <50 °F (-20 °C to <10 °C)
95%: 50 °F to <86 °F (10 °C to <30 °C)
75%: 86 °F to <104 °F (30 °C to <40 °C)
45%: 104 °F to 122 °F (40 °C to 50 °C)
Storage temperature and humidity-4 °F to 158 °F (-20 °C to 70 °C), <95% RH
Operating altitude0 to 6561 ft (2000 m)
Transient protectionN/A6.00 kV (1.2/50μS surge)
Pollution degree2
IP ratingIP 52IP 40
Drop test3.28 ft (1 m)
Power supply4 x AA (alkaline)8 x AA (alkaline)
Power consumption (typical)70 mAHi mode: 70 mA
Loop mode with Clamp: 90 mA
Consumption without signal transmission: 10 mA
Battery lifeApprox. 25 hHi mode: approx. 25 h
Loop mode: approx. 18 h
Low battery indicationYes
FuseN/A1.6 A, 700 V, fast-acting,
Ø 6x32mm
Dimensions (L x W x H)Approx. 7.2 x 2.95 x 1.69 in
(183 x 75 x 43 mm)
Approx. 7.2 x 3.66 x 1.97 in
(183 x 93 x 50 mm)
WeightApprox. 0.6 lb (0.27 kg)Approx. 1.25 lb (0.57 kg)
Certifications